| LJ-01 Straight 2-Way | 8.3/14.4 kV class | 200 A continuous | 200 A separable loadbreak interface | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | Loadbreak-compatible Not a standalone fault interrupter | Pad-mounted or vault-installed; straight-through feeder connection | Verify IEEE 386 interface compatibility, cable diameter range, and tested assembly fault rating |
| LJ-02 Straight 3-Way | 8.3/14.4 kV class | 200 A continuous | Three 200 A loadbreak ways | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | Feeder sectionalizing Switching requires certified elbows and operating tools | Compact underground junction cabinet | Check phase spacing, parking provisions, grounding arrangement, and accessory ratings |
| LJ-03 Straight 4-Way | 8.3/14.4 kV class | 200 A continuous | Four 200 A loadbreak ways | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | Multi-feeder operation Use only with approved switching sequence | Networked distribution vault or pad-mounted cabinet | Confirm enclosure heat dissipation, cable bend radius, and accessibility for live-line tools |
| LJ-04 4-Way with Parking Provisions | 8.3/14.4 kV class | 200 A continuous | Two to four 200 A loadbreak ways plus parking interfaces | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | Maintenance-oriented Parking position is not an energized switching position | Pad-mounted transformer or sectionalizing cabinet | Verify dead-front requirements, parking bushing rating, and insulating cap compatibility |
| LJ-05 Dead-Front 2-Way | 8.3/14.4 kV class | 200 A continuous | 200 A dead-front separable connectors | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | Touch-safe configuration Loadbreak operation only when connector system is qualified | Below-grade vault or compact metal-enclosed gear | Confirm shield continuity, concentric-neutral bonding, and water-sealing performance |
| LJ-06 Dead-Front 3-Way | 8.3/14.4 kV class | 200 A continuous | Three 200 A dead-front ways | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | Sectionalizing Requires system-level switching procedure | Underground distribution network junction | Check cabinet ingress protection, operating clearance, and cable termination dimensions |
| LJ-07 Dead-Front 4-Way | 8.3/14.4 kV class | 200 A continuous | Four 200 A dead-front ways | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | High-connectivity layout Not an automatic interrupter | Large underground vault or pad-mounted enclosure | Verify total cable loading, thermal derating, phase identification, and fault-duty coordination |
| LJ-08 Elbow-Style 2-Way | 8.3/14.4 kV class | 200 A continuous | 200 A elbow-style loadbreak connections | 95 kV BIL | 8 kA rms symmetrical, 0.17 s | 13 kA peak | Routine feeder switching Use only with matching interface and operating tool | Transformer primary or compact switchgear compartment | Confirm elbow probe dimensions, interface class, cable insulation diameter, and grounding point |
| LJ-09 Elbow-Style 3-Way | 8.3/14.4 kV class | 200 A continuous | Three 200 A elbow-style ways | 95 kV BIL | 8 kA rms symmetrical, 0.17 s | 13 kA peak | Feeder transfer Switching duty depends on the complete elbow assembly | Pad-mounted switch or transformer junction | Check parking stand arrangement, phase-to-phase clearance, and cable pulling direction |
| LJ-10 Elbow-Style 4-Way | 8.3/14.4 kV class | 200 A continuous | Four 200 A elbow-style ways | 95 kV BIL | 8 kA rms symmetrical, 0.17 s | 13 kA peak | Multi-way switching Requires approved sequence and isolation controls | Compact multi-circuit distribution enclosure | Verify enclosure ventilation, cable bend radius, and compatibility of all elbows and caps |
| LJ-11 High-Fault 2-Way | 8.3/14.4 kV class | 200 A continuous | 200 A loadbreak interface | 95 kV BIL | 12.5 kA rms symmetrical, 0.17 s | 20 kA peak | Higher available fault level Junction rating does not replace upstream protection | Industrial feeder or utility substation secondary | Require certified short-time and peak withstand test data for the complete assembly |
| LJ-12 High-Fault 3-Way | 8.3/14.4 kV class | 200 A continuous | Three 200 A loadbreak ways | 95 kV BIL | 12.5 kA rms symmetrical, 0.17 s | 20 kA peak | Industrial sectionalizing Switching capability must be stated for the installed connectors | Industrial or utility-grade pad-mounted gear | Check protective-device clearing time, enclosure bracing, and cable termination fault rating |
| LJ-13 High-Fault 4-Way | 8.3/14.4 kV class | 200 A continuous | Four 200 A loadbreak ways | 95 kV BIL | 12.5 kA rms symmetrical, 0.17 s | 20 kA peak | Network-duty junction Not intended to interrupt fault current | High-density distribution vault or metal-enclosed assembly | Confirm bus and enclosure withstand, internal arc requirements, and access controls |
| LJ-14 Outdoor Sealed 2-Way | 8.3/14.4 kV class | 200 A continuous | 200 A loadbreak interface with sealed cable entries | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | Outdoor switching Use only within the tested environmental and connector system limits | Outdoor pad, pole-base, or weather-resistant cabinet | Verify enclosure IP/NEMA classification, UV resistance, corrosion protection, and condensation control |
| LJ-15 Transformer-Riser 2-Way | 8.3/14.4 kV class | 200 A continuous | 200 A riser and transformer-side loadbreak ways | 95 kV BIL | 10 kA rms symmetrical, 0.17 s | 16 kA peak | Transformer connection Loadbreak operation is limited to the connector system’s certified duty | Transformer primary compartment or riser termination cabinet | Check transformer bushing interface, cable shielding, phase spacing, and inrush-related operating procedures |