| Power circuit and motor ratings |
| Motor supply voltage | Rated line-to-line voltage and phase shown on the motor nameplate. | Choose a starter whose contactor operational voltage rating covers the supply. Confirm the motor is connected for that voltage, especially on dual-voltage motors. | Common three-phase systems include 208–230 V, 380–415 V, and 440–480 V. Verify the actual site supply and equipment ratings. |
| Motor full-load current | Nameplate full-load current (FLA), in amperes, at the actual voltage and connection. | Use the nameplate current as the primary sizing reference. Select an overload relay whose adjustment range includes that current, then set it according to the motor and applicable installation rules. | A motor marked 9.2 A at 400 V needs an overload range that includes 9.2 A; do not size only from motor power. |
| Contactor utilization rating | Operational current rating at the application voltage and utilization category. | For ordinary squirrel-cage motor starting and switching, check the contactor’s AC-3 rating under IEC terminology. Its applicable rating should be at least the motor’s operating current. | Do not substitute an AC-1 resistive-load rating for an AC-3 motor-duty rating. |
| Indicative motor current | Approximate current for standard three-phase induction motors. | Use these figures only for preliminary planning. Efficiency, power factor, motor design, and supply voltage change actual current; confirm the nameplate before selection. | At 400 V, typical approximate currents are: 2.2 kW ≈ 4.8 A; 4 kW ≈ 8.5 A; 7.5 kW ≈ 15 A; 11 kW ≈ 22 A. |
| Starting method and frequency | Direct-on-line, reversing, or another starting arrangement; expected starts per hour and operating duty. | Confirm the starter and contactor are suitable for the required switching frequency and duty. Reversing applications require an interlocked reversing arrangement. | A standard single contactor starter is not, by itself, a reversing starter. |
| Overload protection | Relay current range, trip class, phase-loss sensitivity, and reset method. | Match the relay range to the motor nameplate current. Select a trip class appropriate to the motor’s acceleration time and load, and coordinate settings with motor and local protection requirements. | Trip classes such as Class 10, 20, and 30 correspond to different overload trip-time characteristics; choose based on the motor application. |
| Short-circuit protection and coordination | Upstream fuse or circuit-breaker type, rating, and coordination with the starter. | Check the manufacturer-independent device coordination data and the applicable installation standard. The overload relay does not replace short-circuit protection. | Verify the assembly’s short-circuit rating against the prospective fault current at the installation point. |
| Control circuit and installation checks |
| Contactor coil voltage | Control supply voltage, AC or DC type, and frequency where applicable. | Match the coil to the control supply, not automatically to the motor supply. Confirm the coil’s permitted voltage range and frequency from its rating. | A 400 V motor supply can be used with a separately supplied 24 V AC or 24 V DC control circuit if the selected coil matches it. |
| Control-circuit contacts | Required auxiliary contacts, contact function, and control-load rating. | Check the number of normally open and normally closed contacts needed for seal-in, interlocking, indication, or PLC interfaces. Confirm their control-duty rating. | Motor switching contacts and auxiliary control contacts have different purposes and ratings. |
| Control protection and wiring | Control-circuit fuse or protective device, wire size, and grounding arrangements. | Protect and wire the control circuit according to the circuit design and applicable electrical code. Keep control and power wiring appropriately separated. | Emergency-stop and stop circuits should be designed to achieve the required safety function; a standard starter alone is not a safety system. |
| Enclosure and environment | Ingress protection, ambient temperature, altitude, ventilation, and mounting location. | Choose an enclosure suitable for dust, moisture, and access conditions. Apply any required derating for temperature, altitude, or confined mounting. | Check the enclosure IP rating and the starter’s stated operating limits for the installation environment. |
| Standards and documentation | Applicable local electrical code and equipment conformity requirements. | Review the starter, contactor, overload relay, and enclosure documentation as a complete assembly. Confirm the required standards for the installation location. | IEC 60947-4-1 covers contactors and motor-starters; applicable national and local requirements may also apply. |
| Selection note: Ratings and motor-current examples are general guidance, not a substitute for the motor nameplate, equipment documentation, fault-current assessment, or local electrical-code requirements. |