| 1. Match the SPD type to the lightning risk | Consider whether lightning current may enter the installation and follow the applicable electrical code and system design. | Designed to handle partial lightning currents; typically considered where an external lightning protection system is present and the required separation distance cannot be maintained. | Designed mainly to limit induced lightning surges and switching surges; commonly used where direct lightning-current handling is not required. | Type selection depends on the site and installation—not just on the largest number printed on the product. |
| 2. Compare Iimp for Type 1 | Iimp is the impulse discharge-current rating tested with a 10/350 μs waveform. Check the rating per protected path or pole and the manufacturer’s connection diagram. | Example only: 12.5 kA per pole, 10/350 μs. The required rating is determined by the lightning-risk assessment and applicable rules. | Iimp is not normally the defining rating for a Type 2-only SPD; check whether the device is actually rated Type 1 or Type 1+2 if this capability is needed. | Do not compare a Type 1 Iimp value directly with a Type 2 In or Imax value: the test waveforms differ. |
| 3. Check In and Imax for Type 2 | In is nominal discharge current; Imax is maximum discharge current. Both are typically specified using an 8/20 μs waveform. | For a Type 1 device, Iimp is the key lightning-current rating. Some combination devices also publish In and Imax. | Illustrative Type 2 profile: In 20 kA and Imax 40 kA per pole, 8/20 μs. These are example values, not universal minimums. | Compare ratings on the same basis and verify the manufacturer’s stated test configuration and per-pole values. |
| 4. Verify the maximum PV voltage | Check the SPD’s maximum continuous operating voltage for PV DC (often identified as UCPV) against the array’s maximum calculated open-circuit voltage. | Must be selected for the PV system’s DC voltage, just like a Type 2 device. | Must also be selected for the PV system’s DC voltage; a high Imax rating does not make an unsuitable voltage rating safe. | Account for the increase in module open-circuit voltage at the site’s lowest design temperature, following the system and code requirements. |
| 5. Confirm the SPD is intended for PV DC | Check the product documentation for PV DC use and the relevant standard, such as IEC 61643-31 for SPDs used on the DC side of photovoltaic installations. | Use a PV-rated Type 1 or Type 1+2 device where the design requires Type 1 protection. | Use a PV-rated Type 2 device where Type 2 protection is appropriate. AC-only ratings do not establish suitability for PV DC. | Confirm polarity, earthing arrangement, maximum PV voltage, and permitted system configuration in the datasheet. |
| 6. Check protection level and wiring | Review the declared voltage protection level (Up) and follow the installation instructions for conductor length, routing, backup protection, and connections. | Choose a Up and installation arrangement compatible with the equipment being protected and the system design. | Apply the same checks; long connecting leads can reduce the protection achieved at the equipment terminals. | Ratings alone do not determine protection performance. Correct coordination and short, properly routed connections matter. |
| 7. Plan coordination and replacement | Check whether protection is needed at the array, inverter, or other locations, and whether the device has a status indicator or replaceable module. | Coordinate with downstream SPDs and the installation’s lightning protection design when Type 1 capability is required. | May be used as a coordinated downstream stage where the design calls for it; follow manufacturer guidance on spacing and coordination. | Use the manufacturer’s coordination tables and replacement instructions. Have selection and installation verified by a qualified professional. |