| Power Transformer | Raises or lowers AC voltage between transmission and distribution levels. | Connects voltage levels; circuit breakers isolate it during faults or maintenance, while CTs and VTs provide measurements for protection and control. | Usually the largest item in a substation. Many power transformers use oil for insulation and cooling. |
| Circuit Breaker | Makes or interrupts electrical current, including fault current, within its rated capability. | A protection relay detects an abnormal condition and sends a trip command; the breaker opens to disconnect the affected circuit. | Installed in line, transformer, bus, or feeder circuits. Interruption technology varies with voltage and design. |
| Disconnect Switch (Isolator) | Provides visible or otherwise verifiable isolation of equipment for safe work. | Typically operated after the circuit breaker has interrupted the load or fault current. It is not generally designed to interrupt normal load current. | Often paired with an earthing switch and mechanical or electrical interlocks. |
| Busbar | Conducts and distributes power among incoming circuits, transformers, and outgoing feeders. | Circuit breakers and disconnect switches connect or separate circuits from the bus, enabling switching and maintenance arrangements. | May be built from rigid conductors or flexible conductors; bus layouts vary by reliability and operational needs. |
| Current Transformer (CT) | Produces a reduced, proportional current signal for measurement and protection circuits. | Feeds current information to meters and protection relays, which use it to monitor load and identify overcurrent or other fault conditions. | Installed around or in series with a conductor. CT secondary circuits require careful handling and should not be left open-circuited while energized. |
| Voltage Transformer (VT/PT) | Provides a scaled voltage signal for metering, protection, and control. | Supplies voltage data to relays and control systems, which may use it with CT measurements to detect abnormal conditions and manage switching. | May be an inductive voltage transformer or a capacitive voltage transformer, depending on the system design and voltage level. |
| Surge Arrester | Limits transient overvoltages, such as lightning- or switching-related surges, by conducting surge current to ground. | Protects connected equipment, such as transformers and switchgear, by diverting surge energy away from insulation, then returns to a high-resistance state. | Connected between a live conductor and the grounding system, often close to the equipment being protected. |
| Protection Relay | Monitors system signals and initiates protective actions when configured operating conditions are met. | Uses inputs from CTs and VTs; when a fault is detected, it sends a trip signal to the relevant circuit breaker. | Usually housed in a control building or panel. Settings and schemes are engineered for the specific power system. |
| Grounding (Earthing) System | Provides a low-impedance path for fault and surge currents and helps control dangerous voltage differences across the site. | Connects equipment enclosures, structures, and surge arresters to a grounding grid, supporting protective operation and personnel safety. | Typically includes buried conductors and bonded connections. Its design considers soil conditions and fault-current requirements. |
| Station Service and DC Supply | Supplies auxiliary AC loads and dependable DC power for control, protection, alarms, and breaker trip circuits. | Battery-backed DC systems help keep essential protection and control functions available when normal AC station service is interrupted. | Common components include batteries, chargers, DC distribution panels, and auxiliary transformers or AC distribution equipment. |