| Temperature measurement accuracy | Often stated as ±2°C or ±2% of the reading, whichever is greater | Useful for identifying temperature differences and prioritizing components for further investigation. | This is a typical specification, not a universal guarantee. Accuracy depends on the instrument, calibration, target, distance, and environment. |
| Detector resolution | Common handheld options range from about 160 × 120 to 640 × 480 pixels | Higher resolution can make small or distant components easier to distinguish and measure. | Resolution alone does not determine measurement accuracy; focus, field of view, and measurement distance also matter. |
| Thermal sensitivity (NETD) | Many inspection cameras specify roughly 50 mK or better; values vary by model | Lower NETD can help reveal subtle temperature contrasts between nearby areas. | NETD describes sensitivity to small temperature differences, not absolute temperature accuracy. |
| Measurement temperature range | Ranges such as approximately −20°C to 550°C are available in some instruments | A suitable range can cover routine panel inspections and hotter components. | Available ranges and accuracy may change across the instrument’s specified temperature bands. |
| Emissivity setting | Adjustable emissivity is common; about 0.95 is often a useful starting point for many non-reflective surfaces | Correct emissivity improves readings from painted, oxidized, or insulated surfaces. | Shiny metal can have low and variable emissivity and may reflect nearby heat sources, making its apparent temperature misleading. |
| Electrical inspection targets | Connections, fuses, breakers, busbars, cable terminations, and phase-to-phase comparisons | Uneven heating under comparable load can help flag loose, overloaded, imbalanced, or deteriorating connections. | A thermal pattern indicates an area for investigation; it does not by itself identify the root cause. |
| Load and operating conditions | Inspect equipment in normal, documented operating conditions whenever safe and permitted | Load information helps distinguish meaningful heating from temperature differences caused by changing demand. | Record load, ambient conditions, distance, and inspection time so follow-up images can be compared fairly. |
| Image focus and measurement distance | Focus carefully and keep the target large enough within the measurement area | Sharp images and adequate target coverage support more dependable temperature readings. | A small target surrounded by hotter or cooler areas can produce a mixed reading; follow the instrument’s distance-to-spot guidance. |
| Interpretation and follow-up | Compare similar components and phases; confirm suspected issues using appropriate electrical tests | Temperature differences can help rank findings for inspection and maintenance. | There is no single temperature-difference threshold suitable for every installation. Apply site procedures and qualified-person judgment. |
| Safety and access | Use the required electrical safe-work practices, PPE, and access controls | Noncontact imaging can support screening from a distance where a safe viewing position is available. | A thermal camera does not make energized equipment safe to approach or open. Follow applicable regulations and site safety procedures. |