| Applicable design standard | Confirm that the proposed tank design follows a standard appropriate to its construction and service. Relevant references can include AWWA D120 for thermosetting fiberglass-reinforced plastic tanks, ASTM D3299 for filament-wound tanks, or ASTM D4097 for contact-molded tanks. | Ask the manufacturer to identify the standard and edition used in the design documents. Check that the standard applies to the tank type and intended duty; a standards reference alone does not establish compliance. |
| Service and design conditions | Review the stated contents, concentration, specific gravity, operating and design temperatures, pressure or vacuum conditions, and indoor or outdoor installation environment. | Request a project-specific design basis and written operating limits. Do not compare quoted capacities or wall thicknesses without checking whether the design conditions are equivalent. |
| Resin compatibility | Check that the resin system and any corrosion barrier are selected for the stored liquid, its concentration, temperature, and cleaning or disinfection process. | Request written chemical-compatibility confirmation for the actual service conditions. A general chemical-resistance chart should not replace project-specific review. |
| Potable-water suitability | For drinking-water applications, verify that wetted materials and the finished tank meet the requirements accepted by the relevant authority or project specification. | Ask for current, scope-appropriate documentation. NSF/ANSI/CAN 61 is one recognized health-effects standard for drinking-water system components; acceptance depends on the jurisdiction and the product’s certification scope. |
| Structural design and loading | Check design loads for the installation, including liquid head, wind, seismic effects where applicable, roof or platform loads, and supports or anchorage. | Request signed or otherwise suitably approved calculations and drawings identifying the assumed loads and support conditions. Confirm that site-specific requirements are included. |
| Manufacturing process and quality controls | Establish whether the tank is filament-wound, contact-molded, or made using another specified process, and how material batches, laminate construction, and production stages are controlled. | Review the inspection and test plan, material traceability records, production records, and nonconformance process. Match the manufacturing route to the design and service requirements. |
| Quality-management certification | Check whether the production facility has a quality-management certification relevant to the project, such as ISO 9001. | Verify the certificate’s validity, issuing certification body, site address, and scope. Certification supports a management-system assessment but is not, by itself, proof that a particular tank meets its design requirements. |
| Inspection and testing | Agree on applicable dimensional checks, visual inspection, leak or hydrostatic testing, and any additional project-specific tests before production begins. | Ask for written acceptance criteria, test procedures, inspection records, and final release documents. Clarify whether customer or third-party inspection is permitted. |
| Drawings, nozzles, and accessories | Check nozzle locations and sizes, manways, vents, ladders, supports, internal components, and connections against the installation layout and piping design. | Review and approve the final general-arrangement and connection drawings before fabrication. Confirm flange drilling, materials, tolerances, and responsibility for accessories. |
| Transport and installation | Assess transport dimensions, lifting points, delivery route, site access, foundation tolerances, and whether the tank is shipped assembled or in sections. | Request a lifting and installation plan, foundation requirements, and clear division of responsibilities for unloading, assembly, and commissioning. |
| Warranty and service support | Review warranty duration, covered components, exclusions, response arrangements, spare parts, and technical support for installation and operation. | Obtain the warranty terms in writing and check that they match the intended service, operating limits, and project location. |
| Commercial and delivery terms | Compare the full scope, including engineering, testing, packaging, shipping, installation support, taxes or duties where applicable, and delivery schedule. | Use like-for-like quotations with documented exclusions and delivery terms. A low purchase price may not include the testing, documentation, or installation support required by the project. |