| 1 | Insulation thermal class | IEC 60085 designates Class F as 155°C and Class H as 180°C. | State the required thermal class and ask whether it applies to the complete insulation system. A thermal class is not, by itself, a permitted ambient temperature or winding-temperature-rise limit. |
| 2 | Winding conductor material | Copper and aluminium are both used in transformer windings. Copper has higher electrical conductivity by volume; aluminium generally requires a larger conductor cross-section for comparable resistance. | Specify the material, conductor dimensions, connection method and any project-specific limits. Compare designs on the required electrical and thermal performance, not material name alone. |
| 3 | Rated voltage and frequency | Common supply frequencies include 50 Hz and 60 Hz. For a given winding and core, magnetic flux is related to the applied voltage-to-frequency ratio (V/f). | Provide rated primary and secondary voltages, frequency, tap range and connection arrangement. Confirm that the design is suitable for the stated V/f and operating conditions. |
| 4 | Conductor size and winding current | Required conductor area depends on current, material, winding geometry, cooling and allowable temperature rise; there is no single current-density value suitable for every transformer. | Request the rated current and winding-loss information for each winding, and have conductor dimensions checked against the specified duty and cooling method. |
| 5 | Insulation materials and construction | Winding insulation may use combinations of conductor covering, turn insulation, layer insulation, barriers and spacers. The materials and arrangement depend on the design. | Ask for the insulation-system thermal class and relevant construction details. Verify that material choices and clearances meet the applicable electrical, thermal and mechanical requirements. |
| 6 | Cooling, duty and temperature rise | Temperature performance depends on losses, loading profile, cooling arrangement, ambient conditions and enclosure or installation conditions. | Specify continuous or cyclic duty, overload requirements, cooling method, maximum ambient temperature and installation altitude where relevant. Confirm the guaranteed temperature-rise limits separately from the insulation class. |
| 7 | Inspection and test documentation | IEC 60076-1 includes general requirements and routine-test provisions for power transformers, including checks such as winding resistance and voltage ratio. | Agree on the applicable standards and test scope before ordering. Request the routine-test report and confirm that nameplate ratings, tap positions and connection details match the purchase specification. |